| Parameter |
Unit |
Data |
| Rated voltage |
kV |
12 |
| Rated current |
A |
630 |
| Rated frequency |
Hz |
50 |
| Rated power frequency withstand
voltage(1min) |
kV |
42 |
| Lightning impulse withstand voltage |
kV |
75 |
| Rated short circuit breaking current |
kA |
12.5/16/20 |
| Rated short circuit making current |
kA |
31.5/40/50 |
|
Switching operations of rated short circuit
switching current |
Time |
30 |
| Rated switching current of single capacitor
bank |
A |
630 |
| Rated short time withstand current |
kA |
12.5/16/20 |
| Rated withstand current(peak) |
kA |
31.5/40/50 |
| Rated duration of short circuit |
s |
4 |
| Mechanical endurance |
Time |
10000 |
| Switching operations of rated current |
Time |
10000 |
| Closing force due to bellow and atmosphere |
N |
80¡À40 |
| Force required to hold contacts open at full
stroke |
N |
120¡À50 |
| Time-limited circuit resistance at rated
compressive force |
¦Ì¦¸ |
¡Ü30 |
| Shelf life |
Years |
20 |
| Contact limit erosion |
mm |
3 |
| Weight of moving parts |
kg |
¡Ü1.5 |