Type HTD3132EB/HTD3142EB

   
¡¡¡¡

Specification

Parameter Unit Data
Rated voltage kV 12
Rated current A 630
Rated frequency Hz 50
Rated power frequency withstand voltage(1min) kV 42
Lightning impulse withstand voltage kV 75
Rated short circuit breaking current kA

16/20

Rated short circuit making current kA 40/50

Switching operations of rated short circuit switching current

Time 30
Rated switching current of single capacitor bank A 630
Rated short time withstand current kA 16/20
Rated withstand current(peak) kA 40/50
Rated duration of short circuit s 4
Mechanical endurance Time 10000
Switching operations of rated current Time 10000
Closing force due to bellow and atmosphere N 80¡À40
Force required to hold contacts open at full stroke N 120¡À50
Time-limited circuit resistance at rated compressive force ¦Ì¦¸ ¡Ü30
Shelf life Years 20
Contact limit erosion mm 3
Weight of moving parts kg ¡Ü1.5

¨ƒ Mechanical data required for the matcded vacuum switchgear

Parameter Unit Data
Clerance between open conatcts mm 10¡À1
Contact connection stroke mm 3.5¡À0.5
Average opening speed m/s 1.0¡À0.25
Average closing speed m/s 0.6¡À0.15
Rated compressive force of contact N 1300/1600¡À100
Contact bouncing duration at closing operation ms ¡Ü2
Out of simultaneity of contact closing and opening ms ¡Ü1

¨ƒ Dimension