Type HTD512

   
      

Specification

Parameter Unit Data
Rated voltage kV 31.5
Rated current A 630
Rated frequency Hz 50
Rated power frequency withstand voltage(1min) kV 85
Lightning impulse withstand voltage kV 175
Rated short circuit breaking current kA

12.5

Rated short circuit making current kA 31.5

Switching operations of rated short circuit switching current

Time 30
Rated switching current of single capacitor bank A  
Rated short time withstand current kA 12.5
Rated withstand current(peak) kA 31.5
Rated duration of short circuit s 2
Mechanical endurance Time 150000
Switching operations of rated current Time 150000
Closing force due to bellow and atmosphere N 160¡À40
Force required to hold contacts open at full stroke N 260¡À50
Time-limited circuit resistance at rated compressive force ¦Ì¦¸ ¡Ü45
Shelf life Years 20
Contact limit erosion mm 3
Weight of moving parts kg ¡Ü1.5

¨ƒ Mechanical data required for the matcded vacuum switchgear

Parameter Unit Data
Clerance between open conatcts mm 16¡À2
Contact connection stroke mm 3.5¡À0.5
Average opening speed m/s 1.3¡À0.10
Average closing speed m/s 0.5¡À0.15
Rated compressive force of contact N 1500¡À150
Contact bouncing duration at closing operation ms ¡Ü2
Out of simultaneity of contact closing and opening ms ¡Ü1

¨ƒ Dimension