Applying ambient conditions:
Ambient temperature: The max. temperature shou1d be +40C. The mix. temperature should be -30C.
The height above sea level shou1d be no higher than l000m.
Wind pressure should be 0n more than 700pa (it is equivalent to wind speed of 34 m/s.)
The air filthy shou1d be within III degree. Frequent1y violent vibration shou1d be forbidden.
The Construction Characteristics:
Construction of ZW8 Vacuum Circuit Breaker:
Integral construction with three-phase in one box
Vacuum circuit breaker
Spring operating mechanism
Insulating system
Conductive 1oop
Box cover/enclosure
Hermetic parts
The feature of ZW28 series
It can be equipped with 50/5,,100/5,200/5,400/5,630/5 current transformer according to customers' requirement.
Outside insulator adopted the material of silicon rubber bushing with high pressure.
Inside insulator adopted compound insulating material.
Inside multiple-taps current mutual transformer can be used for loading current protection.
Bifilar-wound current mutual transformer can be used for protection and measurement.
1f additionally assembled with voltage mutual transformer, auto-recloser, auto-sectional switch, then autoimmunization of power distribution protection and the function of FOUR REMORE can be achieved. And it is additionally fitted with compound controller (in order to eliminate strong current while closing switch)
It can be mounted isolated switch.
Features Of ZW Series VCB:
It is the optimum match between the vacuum circuit breaker and operating mechanism.
Having been adopted the vacuum interrupter with vertical magnetic field, which has strong breaking and overloading current capacity to make the
VCB reach higher technical specification.
It is absolutely safe and reliable.
It can meet customer's requirement for its various specifications.
Good qua1ity and reasonable price, it is a best choice for un-oiled remaking to town and country's electric net.
Specification sheet :
Name |
Unit |
Data |
Rated Voltage |
kV |
12 |
Rated current |
A |
630 |
Rated power-frequency withstand voltage(dry test/wet test) |
kV |
42/34 |
Rated short time withstand current |
kA |
<20 |
| Rated withstand current(peak) |
kA |
<50 |
Rated short-circuit breaking current |
kA |
<20 |
Rated short-circuit making current |
kA |
<50 |
Rated lighting impulse withstand voltage |
kA |
75 |
Rated duration of short circuit |
S |
4 |
| Rated making operations of short circuit breaker |
Cycles |
30 |
| Other Technical Data |
| Rated voltage of store energy motor |
V |
DC220, 110 AC220, 110 |
| Power of energy-stored motor |
W |
200 |
Power of opening and closing coil |
V |
~220,-110,-220 |
Current of closing coil |
A |
1.1 |
Current of opening coil |
A |
0.5?? 0.99? 0.51 |
Current of overloading release |
A |
5 |
|